The influence of low resistance grounding system in delta side of transformer on differential protection and its solutions


In the system with lead in delta side of transformer grounded by low resistance, differential current arises in the traditional differential protection when having grounding fault beyond protected zone in this side, which may cause differential protection mal-operation. The paper analyzes the two schemes by contrast. The first scheme is differential… (More)