The Effect of Changing the Conductors Layout on the Magnetic Field Level Generated Around Conductors of 132kv High Tension Transmission Lines Extended In Kirkuk City

  • Maryam Mohammed Falih
  • Published 2015

Abstract

In this research, the magnetic flux density generated by the 132 kV double vertical line circuit configuration has been studied using shadow method and the results were compared with measured values. The behavior of different geometric configurations of power lines had been simulates to determine which of them produce less "magnetic. Obtained results indicate that the strength of magnetic field is still below the threshold defined by the International Commission for Protection Against Ionizing Radiation Protection (ICNIRP). Results indicate that the Changing of the Standard dual vertical channel configuration into a dual vertical configuration of the modified phase layout reduce the magnetic flux density on the ground surface in midchannel (X = 0), of about (65. %).

Cite this paper

@inproceedings{Falih2015TheEO, title={The Effect of Changing the Conductors Layout on the Magnetic Field Level Generated Around Conductors of 132kv High Tension Transmission Lines Extended In Kirkuk City}, author={Maryam Mohammed Falih}, year={2015} }