Proposed transmission smart grids will use a digital platform for the automation of substations operating at voltage levels of 110 kV and above. The IEC 61850 series of standards, released in parts over the last ten years, provide a specification for substation communications networks and systems. These standards, along with IEEE Std 1588-2008 Precision Time Protocol version 2 (PTPv2) for precision timing, are recommended by the both IEC Smart Grid Strategy Group and the NIST Framework and… 
Roadmap for Digital Control System (DCS) Implementation in Utility Substations
TLDR
The assessment of Digital Control System (DCS)/SAS generally implemented across power Utilities, based on the IEC 61850 Edition 1 is presented, bringing the view of global SAS implementations and industry best practices.
System-Level Tests of Transformer Differential Protection Using an IEC 61850 Process Bus
The IEC 61850 family of standards for substation communication systems was released in the early 2000s and includes IEC 61850-8-1 and IEC 61850-9-2 that enable Ethernet to be used for process-level
Investigation of an IEC 61850 standard-based process bus implementation of a protection and control scheme for parallelly connected transformers
TLDR
It is shown that process bus information such as the high voltage switchgear status information of primary plant in the yard, can be used to improve the substation protection and control systems.
Performance Analysis of IEC 61850 Sampled Value Process Bus Networks
TLDR
The role a process bus plays in an IEC 61850-based substation automation system is examined and test methods that can be used to assess the adequacy of a network are proposed and examples of the application and interpretation of these tests are provided.
Network Interactions and Performance of a Multifunction IEC 61850 Process Bus
TLDR
A method, based on the Multiple Spanning Tree Protocol (MSTP) and virtual local area networks, is presented that separates management and monitoring traffic from the rest of the process bus, and a quantitative investigation of the interaction between various protocols used in a process bus is described.
Advanced networks for distributed measurement in substation automation systems
TLDR
The results demonstrate that the commonly adopted Rapid Spanning Tree Protocol (RSTP) is not suitable for the most demanding measurement applications due to the loss of measurement samples during the network reconfiguration time (up to 200 ms), and more advanced redundancy protocols are able to satisfy also the most strict availability requirements, as suggested by the simulation results.
Implementation of a dependability framework for smart substation automation systems : application to electric energy distribution
TLDR
This work aims to develop methods for testing the IEC 61850 enabled substation automation systems, especially on the process and the bay levels, in a platform dedicated for research tasks, to improve the designed system dependability.
Direct Evaluation of IEC 61850-9-2 Process Bus Network Performance
This letter presents a technique to assess the overall network performance of sampled value process buses based on IEC 61850-9-2 using measurements from a single location in the network. The method
An IEC 61850-Compliant distributed PMU for electrical substations
TLDR
A measurement architecture based on process bus and sampled values synchronized with IEEE 1588-2008 is proposed, so that voltage and current signals are acquired by a Merging Unit, while the signal processing is performed on a IED (Intelligent Electronic Device) that uses a new algorithm for synchrophasor measurement.
A New IED With PMU Functionalities for Electrical Substations
TLDR
A new distributed architecture to measure synchrophasors in power substations, inspired by the standards IEC 61850 is proposed and suitably modified to have high performance also in terms of response time in presence of step change conditions.
...
...

References

SHOWING 1-10 OF 25 REFERENCES
Performance of IEC 61850-9-2 Process Bus and Corrective Measure for Digital Relaying
TLDR
A corrective measure to address the issues with the several sampled value messages lost and/or delayed by proposing the sampled value estimation algorithm for any digital substation relaying is presented.
Smart High Voltage Substation Based on IEC 61850 Process Bus and IEEE 1588 Time Synchronization
  • Jim Mcghee, M. Goraj
  • Engineering, Computer Science
    2010 First IEEE International Conference on Smart Grid Communications
  • 2010
This paper describes the experience from the world first installation of Smart High Voltage substation with IEC 61850 Process Bus where IEEE 1588 Time Synchronization and dynamic multicast filtering
Protection performance testing in IEC 61850 based systems
TLDR
This paper will investigate new approaches for testing IEC 61850 compatible relays based on the Real Time Digital Simulator (RTDS) and the OMICRON test set, and the structure and implementation of a new RTDS system based on IEC61850 standard.
Evaluation of process bus reliability
TLDR
This paper presents the development and application of an established platform for evaluating process bus applications and various types of background traffic over different network architectures and their impact on the process bus reliability are discussed.
Real time simulation and testing using IEC 61850
TLDR
A successful implementation for IEC 61850 messaging on a real time simulator using the GTNET card is presented and the key design criteria is discussed, as an example of the effectiveness of the RTDS simulator as a testing tool, tests were run in which the “quality” information contained in the IEC61850 data was dynamically changed.
Real Time Simulation Testing Using IEC 61850
TLDR
A successful hardware implementation for IEC 61850 messaging on a real time simulator is presented and the key design criteria is discussed, which will allow real time simulations to be repeatable and dependable.
Reliable, Fast, and Deterministic Substation Communication Network Architecture and its Performance Simulation
  • M. Thomas, I. Ali
  • Computer Science, Engineering
    IEEE Transactions on Power Delivery
  • 2010
TLDR
Improved reliability, availability, and survivability of the SAS are demonstrated through the unique architectural features of this SCN, whereas the end-to-end (ETE) time-delay performance of the SCN architecture is evaluated with the help of simulation.
Vision for a smart transmission grid
  • D. Tholomier, L. Jones
  • Engineering
    2010 IREP Symposium Bulk Power System Dynamics and Control - VIII (IREP)
  • 2010
This paper has provided a vision for the smart transmission grid from the perspective of system protection and control based on IEC 61850 standard. More and more major utilities are beginning to
NIST Framework and Roadmap for Smart Grid Interoperability Standards, Release 1.0
TLDR
Develop a summary of power reliability and quality characteristics that affect price and availability (supply side) and desirability (demand side), and survey existing price communications and develop harmonized specification.
Smart Grid technology review within the Transmission and Distribution sector
TLDR
This paper summarizes smart grid technologies within the T&D sector that in terms of technology readiness are superior to other technologies, and are expected to be deployed in the near future.
...
...