Switching Overvoltage Characteristics of $\pm $1100-kV UHVDC Converter Station

@article{Wang2015SwitchingOC,
  title={Switching Overvoltage Characteristics of \$\pm \$1100-kV UHVDC Converter Station},
  author={Dongju Wang and Hao Zhou and Xu Deng},
  journal={IEEE Transactions on Power Delivery},
  year={2015},
  volume={30},
  pages={1205-1212}
}
The present study analyzed the characteristics of switching overvoltage, and discussed in detail the main influencing factors and worst-case conditions of switching overvoltage in the ±1100-kV ultra-high-voltage direct-current (UHVDC) converter station. The results showed that ac bus overvoltage was produced by oscillation, and would not be a threat to the equipment in the converter station. The results also showed there were two cases for overvoltage on related valves. In the first case, the… CONTINUE READING

References

Publications referenced by this paper.
SHOWING 1-10 OF 18 REFERENCES

Insulation coordination for xiluodu converter station of kV UHVDC power transmission project from xiluodu to zhexi

  • X. Deng, D. Wang, H. Zhou, X. Chen, A. Xu, Y. Shen
  • High Voltage Eng., vol. 38, no. 12, pp. 3198–3205…
  • 2012

R&D progress of kV UHVDC technology

  • Z. Liu, L. Gao, Z. Wang, J. Yu, J. Zhang, L. Lu
  • B4_201_, CIGRE session .
  • 2012