Propagation properties of PD-induced electromagnetic wave in 66 kV GIS model tank with L branch structure

Abstract

The authors investigated the effects of a corner that affects the transmission characteristics of a partial discharge (PD) induced electromagnetic (EM) wave, using a gas insulated switchgear (GIS) model with an L-shaped branch. The authors also experimentally investigated the change of amplitude of PD-induced EM wave around the passage of the Lshaped part… (More)