This paper analytically determines the nondetection zone (NDZ) of an active islanding detection method, and proposes a solution to obviate the NDZ. The method actively injects a negative-sequence current through the interface voltage-sourced converter (VSC) of a distributed generation (DG) unit, as a disturbance signal for islanding detection. The estimated magnitude of the corresponding negative-sequence voltage at the PCC is used as the islanding detection signal. In this paper, based on a… CONTINUE READING