Modeling Power Transformers to Support the Interpretation of Frequency-Response Analysis

@article{Mitchell2011ModelingPT,
  title={Modeling Power Transformers to Support the Interpretation of Frequency-Response Analysis},
  author={S. D. Mitchell and J. S. Welsh},
  journal={IEEE Transactions on Power Delivery},
  year={2011},
  volume={26},
  pages={2705-2717}
}
A power transformer will yield a frequency response which is unique to its mechanical geometry and electrical properties. Changes in the frequency response of a transformer can be potential indicators of winding deformation as well as other structural and electrical problems. A diagnostic tool which leverages this knowledge in order to detect such changes is frequency-response analysis (FRA). To date, FRA has been used to identify changes in a transformer's frequency response but with limited… CONTINUE READING
Highly Cited
This paper has 47 citations. REVIEW CITATIONS

24 Figures & Tables

Topics

Statistics

0510201620172018
Citations per Year

Citation Velocity: 6

Averaging 6 citations per year over the last 3 years.