Failure Analysis and Treatment for MICROREC K4.1 Excitation Regulator "Watchdog"

@inproceedings{Feng2010FailureAA,
  title={Failure Analysis and Treatment for MICROREC K4.1 Excitation Regulator "Watchdog"},
  author={Hou Feng},
  year={2010}
}
The NO.1 electric generator of Shenhua Guohua zhungeer power,which is made by Alstom company had a sudden alarm of MICROREC K4.1 Brushless excitation regurator "watchdog",after the on-the-spot inspection,it has been found that the Control Processor RDSP1 of excitation regurator has been damaged.The upgrade of the system in RDSP1 has been made,and Parameter has been re-uploaded in order to solve the problem.