Exposure to 50 Hz magnetic field in apartment buildings with built-in transformer stations in Hungary.

@article{Thurczy2008ExposureT5,
  title={Exposure to 50 Hz magnetic field in apartment buildings with built-in transformer stations in Hungary.},
  author={Gy{\"o}rgy Thur{\'o}czy and G{\'a}bor J{\'a}nossy and No{\'e}mi Nagy and J{\'o}zsef Bakos and Judit Szab{\'o} and G{\'a}bor C. Mezei},
  journal={Radiation protection dosimetry},
  year={2008},
  volume={131 4},
  pages={469-73}
}
Exposure to 50 Hz magnetic field (MF) was evaluated in 31 multi-level apartment buildings with built-in step-down transformer stations. In each building, three apartments were selected: one apartment located immediately above the transformer room (index apartment), one located on the same floor and one on a higher floor. The mean value of measured MFs was 0.98 microT in apartments above transformers, 0.13 microT on the same floor, and 0.1 microT in on higher floors. The mean measured MF value… CONTINUE READING