Transformer inrush currents are highmagnitude, harmonic-rich currents generated when transformer cores are driven into saturation during energization. These currents have undesirable effects, including potential damage or loss-of-life to the transformer, protective relay misoperation, and reduced power quality on the system. Controlled transformer switching can potentially eliminate these transients if residual core and core flux transients are taken into account in the closing algorithm. This… CONTINUE READING
Highly Cited
This paper has 76 citations. REVIEW CITATIONS