Dual three-winding transformer equivalent circuit matching leakage measurements

@article{Len2009DualTT,
  title={Dual three-winding transformer equivalent circuit matching leakage measurements},
  author={Francisco de Le{\'o}n and Juan Jose Su{\~n}ol Martinez},
  journal={2009 IEEE Power & Energy Society General Meeting},
  year={2009},
  pages={1-1}
}
An equivalent circuit for the leakage inductance of three-winding transformers is presented. The model is derived from the principle of duality (between electric and magnetic circuits) and matches terminal leakage inductance measurements. The circuit consists of a set of mutually coupled inductances and does not contain negative inductances. Each inductance can be computed from both: the geometrical information of the windings and from terminal leakage measurements taking two windings at a time… CONTINUE READING

Similar Papers

Citations

Publications citing this paper.
SHOWING 1-10 OF 32 CITATIONS

Duality Derived Transformer Models for Low-Frequency Electromagnetic Transients—Part I: Topological Models

  • IEEE Transactions on Power Delivery
  • 2016
VIEW 10 EXCERPTS
CITES METHODS & BACKGROUND
HIGHLY INFLUENCED

Duality-Based Transformer Model Including Eddy Current Effects in the Windings

  • IEEE Transactions on Power Delivery
  • 2015
VIEW 4 EXCERPTS
CITES BACKGROUND & METHODS
HIGHLY INFLUENCED

Leakage Flux Modeling of Multiwinding Transformers for System-Level Simulations

  • IEEE Transactions on Power Electronics
  • 2018
VIEW 1 EXCERPT
CITES BACKGROUND

References

Publications referenced by this paper.