Breakdown electric field calculations of hot SF/sub 6/ for high voltage circuit breaker applications

@article{Yousfi2005BreakdownEF,
  title={Breakdown electric field calculations of hot SF/sub 6/ for high voltage circuit breaker applications},
  author={Mohammed Yousfi and Ph. Robin-Jouan and Z. Kanzari},
  journal={IEEE Transactions on Dielectrics and Electrical Insulation},
  year={2005},
  volume={12},
  pages={1192-1200}
}
The critical reduced electric field strengths of hot SF/sub 6/ corresponding to the dielectric recovery phase of a high voltage circuit breaker are calculated for a large temperature range (300-3000 K). Calculations are based on a multi-term Boltzmann equation solution using, in comparison to the literature works, improved cross section sets for the interactions of electrons with various SF/sub 6/ dissociated products. The obtained critical electric fields show a reasonable agreement with the… CONTINUE READING

Citations

Publications citing this paper.
SHOWING 1-10 OF 11 CITATIONS

Breakdown Electric Field Calculation of Hot SF6 and Its Application to High Voltage Circuit Breakers

  • 2012 IEEE 58th Holm Conference on Electrical Contacts (Holm)
  • 2012
VIEW 4 EXCERPTS
CITES METHODS & BACKGROUND
HIGHLY INFLUENCED

Numerical calculation and experimental study on breaking characteristics for high voltage SF6 circuit breaker

  • 2017 4th International Conference on Electric Power Equipment - Switching Technology (ICEPE-ST)
  • 2017
VIEW 1 EXCERPT
CITES METHODS

Influence of copper contamination on dielectric breakdown properties of high-temperature SF6 gas based on Boltzmann equation analysis

  • 2015 3rd International Conference on Electric Power Equipment – Switching Technology (ICEPE-ST)
  • 2015

Electro-gas model breaking of capacitive currents within high voltage SF6 circuit breaker

  • 2011 XXIII International Symposium on Information, Communication and Automation Technologies
  • 2011
VIEW 1 EXCERPT
CITES METHODS

Research and development of self-energy SF6 circuit breaker on the breaking capacity

  • 2011 1st International Conference on Electric Power Equipment - Switching Technology
  • 2011
VIEW 1 EXCERPT
CITES BACKGROUND

References

Publications referenced by this paper.
SHOWING 1-6 OF 6 REFERENCES

Numerical and Experimental Analysis of the Propagation of Hot Arc Plasma in High Voltage Circuit-breakers’

Ph. Robin-Jouan, N. Kairouani
  • Proc. Conf. Gas Discharges and Their Applications, Liverpool, UK,
  • 2002

Measurement of the Photodetachment Cross Section of the Negative Ion of Fluorine

A. Gleizes S. Vacquie, M. Sabsabi
  • Phys . Rev . A
  • 1987

Solution of the Boltzmann Equation with Ionization and Attachment: Application to SF ’

M. Yousfi, P. Sigur, T. Vassiliadis
  • J. Phys. D: Appl. Phys,
  • 1985

Similar Papers