A comparison of overvoltage control methods during three-phase reclosing varying the length of shunt compensated transmission lines

Abstract

The overvoltage phenomena due to three-phase reclosing of shunt compensated extra high voltage (EHV) transmission lines are analyzed and verified by PSCAD/EMTDC simulation. The study made in an actual 500 kV AC transmission system considers three alternatives in order to limit overvoltages during line reclosing: a developed synchronous switching method, the… (More)