In this paper, the orthogonal collocation technique is utilized to solve the Poppe method equations for heat and mass transfer in counter flowing wet-cooling towers. The six differential equations for unsaturated and supersaturated air from the Poppe method are simplified, yielding three differential equations that use the Heaviside function. The humidity(More)