A reduced wall 138kV HPOF pipe-type cable having a 700 kcmil (355 mm2) compact round copper conductor and 348 mils (8.8 mm) of insulation and two types of joints have been developed for re-conductoring existing 69kV HPOF feeders utilizing 5 inch (127 mm) outside diameter pipes on the Florida Power & Light Company (FP& L) system. Laboratory test results on(More)